HLC-4XQ01CY Definite Purpose Contactor

HLC-4XQ01CY Definite Purpose Contactor

Model No.︰4P/25A/24V

Brand Name︰HONGLI

Country of Origin︰China

Unit Price︰US $ 13.75 / pc

Minimum Order︰1000 pc

Inquire Now

Product Description

Application & Ordering information

1 、Application

HLC-4XQ01CY definite purpose contactors (4-pole ,25A ) are ideal for(HVAC) air conditioning, refrigeration, heating, data processing, welding, elevators, hoists & cranes, lighting, pools & spas and food service equipment.

2 、Ordering information

HL C - 4X Q 01 CY
Hongli Electric Contactor Factory Bulk Pack 4P 24VAC 25 FLA #10-32 Combo screw with dual QC

Product Feature

Detailed Product Description

Unique amortization system to eliminate contact bounce
Low cost

• Accessories modification quickly and easily without using tools

Various kinds of terminals for customers' special requirements
Easy to change the coil
General amounting size, easy for replacement
Can be combined with a thermal overload relay to form an electromagnet starter to protect the line in which overload operation may occur
Double E magnet assembly providing optimal performance with reduced power consumption
Effective dustproof cover available
Silver Cadmium Oxide contacts provide long electrical endurance.
Class F high temperature insulated coils are standard.

Technology Data

NUMBER
OF
POLES

COIL
VOLTAGE
50/60HZ

FULL
LOAD
AMPS

LINE VOLTAGE

LOCKED ROTOR AMPS

RESISTIVE SMPS RATING

MAXIMUM HORSEPOWER

BOX QUANTITY

APPROX UNIT WEIGHT

VOLTAGE

SINGLE
PHASE

THREE
PHASE

20FLA-3POLE

3

24
110/120
280/240
277

20

240/277
480
600

120
100
80

30
30
30

110/120
200/240
480/600

1.5
3
-

-
7.5
7.5

25

.45 kg

25FLA-3POLE

3

24
110/120
280/240
277

25

240/277
480
600

150
125
100

35
35
35

110/120
200/208
240/277
480
600

2
-
5
-
-

-
7.5
10
25
20

25

.45 kg

30FLA-3POLE

3

24
24
110/120
110/120
208/240
208/240
277

30

240/277
480
600

180
150
120

40
40
40

110/120
200/208
240/277
480
600

2
-
5
-
-

-
10
10
15
20

25

.45 kg

40FLA-3POLE

3

24
24
110/120
110/120
208/240
208/240
277

40

240/277
480
600

240
200
160

50
50
50

110/120
200/208
240/277
480
600

3
-
7.5
-
-

-
10
10
20
25

25

.45 kg

OTHER SPECIFCATIONS

20-30 FLA

40 FLA

Line and Load Terminals

#10-32 screw*

Box Lug

Wire Size Awg Min-Max

16-8**

14-4 Cu/AL

Tightening Torque(Recommended)

22 in ibs

40 in ibs

Quick Connects:power Terminals Coil Termainals

Dual 250 QC
Dual 250 qc(2)***

Dual 250 QC
Dual 250 qc(2)***

Covers

Optional

Standard

Insulation System

130℃ Class B

130℃ Class B

*Stranding must be split for #8 wirt. **(1)#6-32 screw and (1).250QC are optional.***Permissible Ambient Temperature: -40℃/65℃ -40F/150F

  COIL TECHNICAL DATA 50/60hz

HLC Series

  Nominal Coil Voltage

24

120

208/240

277

480

  Maximum Pickup Volts

18

88

177

220

384

  Drop-Out Volts Range

6-15

20-70

40-140

65-185

150-270

  Nominal Inrush VA@50Hz

65

65

65

65

65

  Nominal Inrush VA@60Hz

60

60

60

60

60

  Nominal Sealed VA@50Hz

7.5

7.5

7.5

7.5

7.5

  Nominal Sealed VA@60Hz

6

6

6

6

6

  Nominal DC Resistance-Ohms

6.6

165

660

880

1320

Specification

HLC-1P,1N,1X,2X,3X,4X series Difinite Purpose Contactor

DownLoad PDF DataSheet