1 、Application
HLC-4XU01CY definite purpose contactors (4-pole ,25A ) are ideal for(HVAC) air conditioning, refrigeration, heating, data processing, welding, elevators, hoists & cranes, lighting, pools & spas and food service equipment.
2 、Ordering information
Product Feature
Detailed Product Description
Technology Data
NUMBER OF POLES
COIL VOLTAGE 50/60HZ
FULL LOAD AMPS
LINE VOLTAGE
LOCKED ROTOR AMPS
RESISTIVE SMPS RATING
MAXIMUM HORSEPOWER
BOX QUANTITY
APPROX UNIT WEIGHT
VOLTAGE
SINGLE PHASE
THREE PHASE
20FLA-3POLE
3
24 110/120 280/240 277
20
240/277 480 600
120 100 80
30 30 30
110/120 200/240 480/600
1.5 3 -
- 7.5 7.5
25
.45 kg
25FLA-3POLE
150 125 100
35 35 35
110/120 200/208 240/277 480 600
2 - 5 - -
- 7.5 10 25 20
30FLA-3POLE
24 24 110/120 110/120 208/240 208/240 277
30
180 150 120
40 40 40
- 10 10 15 20
40FLA-3POLE
40
240 200 160
50 50 50
3 - 7.5 - -
- 10 10 20 25
OTHER SPECIFCATIONS
20-30 FLA
40 FLA
Line and Load Terminals
#10-32 screw*
Box Lug
Wire Size Awg Min-Max
16-8**
14-4 Cu/AL
Tightening Torque(Recommended)
22 in ibs
40 in ibs
Quick Connects:power Terminals Coil Termainals
Dual 250 QC Dual 250 qc(2)***
Covers
Optional
Standard
Insulation System
130℃ Class B
*Stranding must be split for #8 wirt. **(1)#6-32 screw and (1).250QC are optional.***Permissible Ambient Temperature: -40℃/65℃ -40F/150F
COIL TECHNICAL DATA 50/60hz
HLC Series
Nominal Coil Voltage
24
120
208/240
277
480
Maximum Pickup Volts
18
88
177
220
384
Drop-Out Volts Range
6-15
20-70
40-140
65-185
150-270
Nominal Inrush VA@50Hz
65
Nominal Inrush VA@60Hz
60
Nominal Sealed VA@50Hz
7.5
Nominal Sealed VA@60Hz
6
Nominal DC Resistance-Ohms
6.6
165
660
880
1320